Sample HTML table 2
Sensor technology
NDIR
Gas sampling method
Diffusion
Gas
Acetylene
Sensor housing
Stainless Steel Body material for Indoor use (buy the optional accessory rain-guard for outdoor installation
Sensing range
0 - 100% LEL (0 - 2.5 % vol.)
Maximum response time (T90)
<40 s
Maximum deviation from linearity
±0.1% vol.
Maximum variation of zero from −20 to +55 °C
±30 ppm/°C
Resolution
0.1% LEL
Maximum non-reproducibility of zero at 20 °C
±500 ppm
Maximum non-reproducibility of sensitivity at 20 °C
<±1000 ppm
Long-term zero drift/month
±500 ppm
MTBF (lamp dependent only)
>10 years for 5 V operation
Ambient humidity
0-95% RH (Non-condensing)
Temperature
From -20 to 60 °C
Sensor lifetime
10 years
Calibration interval
Recommend recalibrating zero and span at least every 30 months