V. Globiots configuration for HMI slave 5.1 Modbus Slave HMI operation HMI will be a Modbus slave to connect to iConnector via RS485 Modbus RTU Every 8 seconds, iConnector use schedule event to write values from other Modbus slaves to HMI HMI will be pre-coded to view these values on HMI screen 5.2 iConnector event configuration After logging in Globiots, to configure Event: right click Device name and select Event. “The List Of Event” page displays as below: • Import Event: Import event from excel file  • Export Event: Export event to excel file  • Add Event: click to add a new event    o Event ID: from 1 to 127 (event ID is only)    o Event name: name of event    o Comment: explain for event    o Priority: Any value     o On Delay: Delay time (second) when condition is true    o Off Delay: Delay time (second) when condition is false    o Logical Operator (AND/OR): Logical Operator for conditions of event    o Parameter: select parameter sent to server when event occur. Only display Real Parameter    o Click “Save” to finish  • Edit: Click to edit event  • Delete: Click to delete event  • Action: Click to configure action for event. An event might have some actions. The List of Actions page displays:     o Add Action: click to add a new action       Action Name: Name of Action       Action Type: Select type of Action. There are 04 type of available action          1. Type 1: 01- Parameter vs constant: Action to assign constant to parameter if condition is true          2. Type 2: 02-parameter vs parameter: Action to assign constant to parameter if condition is true and false          3. Type 3: Action to assign value of source parameter to value of destination parameter if condition is true          4. Type 4: Action to assign value of source parameter to value of destination parameter if condition is true and false       Repeat: tick to implement action once condition is still true. If Repeat: is not ticked, the action only is implemented when condition from FALSE to TRUE.       Value true: constant assigned to parameter when condition is true       Value false: constant assigned to parameter when condition is false       Write Parameter: Destination parameter which is assigned value       Read Parameter: Source parameter        True Parameter: Source parameter if condition is true       False Parameter: Source parameter if condition is false       Save: click “save” to finish    o Edit: click to edit action of event    o Delete: click to delete actionNote: Written parameter in action must have address in range 3000-307F  • Condition: click to configure condition of event. An event might have one or multi conditions. Value of total condition is formed from logical operator of multi conditions    o Add Condition: click to add new condition       Condition Name: Name of condition       Condition Type: Type of condition. There are 3 types of condition        + Type 1: 01- Parameter vs constant: Compare value of parameter to constant        + Type 2: 02-parameter vs parameter: Compare value of parameter to value of another parameter        + Type 3: 03- Parameter (bit) vs constant: Compare value of bit complex of parameter to constant       Condition: Compare value of a parameter to constant or value of a parameter to value of another parameter. Compare Operators are less than, less than or equal to, equal to, not equal, greater than, greater than or equal to       Click “Save” to finish    o Edit: click to edit condition of event    o Delete: click to delete a condition of event       Note:        Each Event have maximum 8 conditions       After configure Event, you must synchronized (refer to 5.11 Synchronize Device for more details)Example: Configure Event to create parameter Power Status:Power Status =1 when iConnector Power Supply > 8 VDC and Main Meter Error=0 in more than 2s.Power Status=0 when iConnector Power Supply <=8 and Main Meter Error=0 in more than 3 s. When event occur, event will be sent to serverConfiguration for this event, condition and action as follow: For schedule written to HMI slave device every 8 second, the event configuration as below: Condition: Condition type: Use condition type 3 (Parameter (bit) vs constant: Compare value of bit complex of parameter to constant), bit 3 Condition parameter: iConnector second parameter will be use Action: Action type: Use action type 3: Action to assign value of source parameter to value of destination parameter if condition is true Source parameter: Parameters from slave devices except HMI slave device Destination parameter: Parameter to HMI slave device