USER GUIDE FOR LEVEL INDICATING CONTROLLER LFC128-2

LFC128-2-MN-EN-01 

JUN-2020

This document is applied for the following products
SKU LFC128-2 HW Ver. 1.0 FW Ver. 1.1
Item Code

LFC128-2 Level Indicating Controller, 4AI/DI, 4DI, 4xRelay, 1xPulse Output, 2 x RS485/ModbusRTU-Slave Communication
   

1. Functions Change Log

HW Ver. FW Ver. Release Date Functions Change
1.0 1.1 JUN-2020

 

     

 

2. Introduction

LFC128-2 is an advanced level display controller. The product integrates Modbus RTU interface to help PLC / SCADA / BMS and any IoT port can connect to monitor. LFC128-2 has a simple yet powerful design with 4 AI / DI, 4 DI, 4 Relays, 1 Pulse pulse output, 2 RS485 Slave ModbusRTU allowing them to connect with multiple devices easily. With advanced technology that provides high stability and reliability, many functions, easy installation with touch screen and friendly interface helps visually monitor level.

LFC128-2-H1.png

3. Specification

Digital Inputs 04 x Ports, opto-coupler, 4.7 kohms input resisrtance, 5000V rms isolation, Logic 0 (0-1VDC), Logic 1 (5-24VDC), Functions: logic status 0/1 or Pulse counting (32 bit counter with max 4kHz pulse)
Analog Inputs

04 x Ports, select between 0-10VDC input or 0-20mA input, 12 bit Resolution, can be configured as Digital input by DIP switch (max 10VDC input)

The AI1 port is a 0-10 VDC / 4-20 mA level sensor connection port

Relay Output 04 x Ports, electro-mechanical Relays, SPDT, contact rating 24VDC/2A or 250VAC/5A, LED indicators
Pulse Output 01 x Ports, open-collector, opto-isolation, max 10mA and 80VDC, On/off control, Pulser (max 2.5Khz, max 65535 Pulses) or PWM (max 2.5Khz)
Communication 02 x ModbusRTU-Slave, RS485, speed 9600 or 19200, LED indicator
Reset button For resetting 02 x RS485 Slave port to default setting (9600, None parity, 8 bit)
Screen type Touch screen
Power supply 9..36VDC
Consumption 200mA @ 24VDC supply
Mounting type Panel mount
Terminal Block pitch 5.0mm, rating 300VAC, wire size 12-24AWG
Working temperature/humidity 0..60 degC / 95%RH non-condensing
Dimension H93xW138xD45
Net weight 390 grams

4. Product Pictures

LFC128-2-H1.png LFC128-2-H2.png
LFC128-2-H3.png LFC128-2-H4.png
LFC128-2-H5.png LFC128-2-H6.png

5. Operation Principle

LFC128-2-H5.png

5.1 Modbus communication

image-1591342596596.png

02 x RS485/ModbusRTU-Slave

Protocol: Modbus RTU

Address: 1 - 247, 0 is the Broadcast address

Baud rate: 9600 , 19200

Parity: none, odd, even

Status indicator LED:

  • Led on: modbus communication OK
  • Led blinking: received data but modbus communication incorrect, due to wrong Modbus configuration: address, baudrate
  • Led off: LFC128-2 received no data, check the connection
Memmap resgisters

READ uses command 03, WRITE uses command 16

Default configuration:

  • Address: 1
  • Baudrate slave 1: 9600
  • Parity slave 1: none
  • Baudrate slave 2: 9600
  • Parity slave 2: none

Modbus Register

Hex adr

# of registers

Description

Range

Default

Format

Property

Comment

0

0

2

device info

 

LFC1

string

Read

 

8

8

1

DI1___DI2: digital status

0-1

 

uint8

Read

H_byte: DI1
L_byte: DI2

9

9

1

DI3___DI4: digital status

0-1

 

uint8

Read

H_byte: DI3
L_byte: DI4

10

A

1

AI1___AI2: digital status

0-1

 

uint8

Read

H_byte: AI1
L_byte: AI2

11

B

1

AI3___AI4: digital status

0-1

 

uint8

Read

H_byte: AI3
L_byte: AI4

12

C

1

AI1: analog value

   

uint16

Read

 

13

D

1

AI2: analog value

   

uint16

Read

 

14

E

1

AI3: analog value

   

uint16

Read

 

15

F

1

AI4: analog value

   

uint16

Read

 

16

10

2

AI1: scaled value

   

float

Read

 

18

12

2

AI2: scaled value

   

float

Read

 

20

14

2

AI3: scaled value

   

float

Read

 

22

16

2

AI4: scaled value

   

float

Read

 

24

18

1

relay 1

0-1

 

uint16

Read

 

25

19

1

relay 2

0-1

 

uint16

Read

 

26

1A

1

relay 3

0-1

 

uint16

Read

 

27

1B

1

relay 4

0-1

 

uint16

Read

 

28

1C

1

open collector ctrl

 

0-3

uint16

Read/Write

0: off
1: on
2: pwm, pulse continuously
3: pulse, when enough pulse number, ctrl = 0

30

1E

2

counter DI1

   

uint32

Read/Write

counter writable, erasable

32

20

2

counter DI2

   

uint32

Read/Write

counter writable, erasable

34

22

2

counter DI3

   

uint32

Read/Write

counter writable, erasable

36

24

2

counter DI4

   

uint32

Read/Write

counter writable, erasable

38

26

2

counter AI1

   

uint32

Read/Write

counter writable, erasable, max frequency 10Hz

40

28

2

counter AI2

   

uint32

Read/Write

counter writable, erasable, max frequency 10Hz

42

2A

2

counter AI3

   

uint32

Read/Write

counter writable, erasable, max frequency 10Hz

44

2C

2

counter AI4

   

uint32

Read/Write

counter writable, erasable, max frequency 10Hz

46

2E

2

DI1: time on

   

uint32

Read/Write

sec

48

30

2

DI2: time on

   

uint32

Read/Write

sec

50

32

2

DI3: time on

   

uint32

Read/Write

sec

52

34

2

DI4: time on

   

uint32

Read/Write

sec

54

36

2

AI1: time on

   

uint32

Read/Write

sec

56

38

2

AI2: time on

   

uint32

Read/Write

sec

58

3A

2

AI3: time on

   

uint32

Read/Write

sec

60

3C

2

AI4: time on

   

uint32

Read/Write

sec

62

3E

2

DI1: time off

   

uint32

Read/Write

sec

64

40

2

DI2: time off

   

uint32

Read/Write

sec

66

42

2

DI3: time off

   

uint32

Read/Write

sec

68

44

2

DI4: time off

   

uint32

Read/Write

sec

70

46

2

AI1: time off

   

uint32

Read/Write

sec

72

48

2

AI2: time off

   

uint32

Read/Write

sec

74

4A

2

AI3: time off

   

uint32

Read/Write

sec

76

4C

2

AI4: time off

   

uint32

Read/Write

sec

128

80

2

counter DI1

   

uint32

Read

counter cannot write, erase

130

82

2

counter DI2

   

uint32

Read

counter cannot write, erase

132

84

2

counter DI3

   

uint32

Read

counter cannot write, erase

134

86

2

counter DI4

   

uint32

Read

counter cannot write, erase

136

88

2

counter AI1

   

uint32

Read

counter cannot write, erase; max frequency 10Hz

138

8A

2

counter AI2

   

uint32

Read

counter cannot write, erase; max frequency 10Hz

140

8C

2

counter AI3

   

uint32

Read

counter cannot write, erase; max frequency 10Hz

142

8E

2

counter AI4

   

uint32

Read

counter cannot write, erase; max frequency 10Hz

256 100 1 modbus address slave 1-247 1 uint16 Read/Write  
257 101 1 modbus baudrate slave 1 0-1 0 uint16 Read/Write 0: 9600, 1: 19200
258 102 1 modbus parity slave 1 0-2 0 uint16 Read/Write 0: none, 1: odd, 2: even

5.2 Reset Button

When holding the reset button for 4 seconds, LFC 128-2 will reset the default configuration to 02 x RS485 / Modbus RTU-Slave.

Default Modbus RTU Configuration:

  • Address: 1
  • Baud Rate: 9600
  • Parity: none

5.3 Digital Input

image-1591342634783.png

Specification:

  • 04 channels DI, isolated
  • Input Resistance: 4.7 kΏ
  • Isolation Voltage: 5000Vrms
  • Logic level 0: 0-1V
  • Logic level 1: 5-24V
  • Function:
    • Read logic 0/1
    • Pulse Counter
5.3.1 Read the logical state 0/1

Logic value in Modbus Memory Map: 0-1

Registers to store logic values in the Modbus Memory Map:

  • DI1__DI2: digital status: stores the logical state of channel 1 and channel 2.
    • H_byte: DI1
    • L_byte: DI2
  • DI3__DI4: digital status: store the logical state of channel 3 and channel 4.
    • H_byte: DI3
    • L_byte: DI4
5.3.2 Pulse Counter

Counter value in Modbus Memory Map, when adding the number exceeds the threshold, it will automatically return: 0 - 4294967295 (32bits)

The register that stores Counter value in the Modbus Memory Map cannot be erased:

  • Counter DI1: stores the logic state of channel 1
  • Counter DI2: stores the logic state of channel 2
  • Counter DI3: store the logic state of channel 3
  • Counter DI4: stores the logic state of channel 4

The register that stores Counter value in the Modbus Memory Map cannot be erased:

  • None reset counter DI1: stores the logic state of channel 1
  • None reset counter DI2: stores the logic state of channel 2
  • None reset counter DI3: stores the logic state of channel 3
  • None reset counter DI4: stores the logic state of channel 4

Pulse Counter Mode:

Low-speed pulse count less than 10Hz with filter, anti-jamming:

  • Set register "counter DI1: filter time" = 500-2000: Channel 1 counts pulses less than 10Hz
  • Set register "counter DI2: filter time" = 500-2000: Channel 2 counts pulses less than 10Hz
  • Set register "counter DI3: filter time" = 500-2000: Channel 3 counts pulses less than 10Hz
  • Set register "counter DI4: filter time" = 500-2000: Channel 4 counts pulses less than 10Hz

High-speed pulse count with max 2KHz frequency without filter:

  • Set register "counter DI1: filter time" = 1: channel 1 counts pulses with Fmax = 2kHz
  • Set register "counter DI2: filter time" = 1: channel 2 counts pulses with Fmax = 2kHz
  • Set register "counter DI3: filter time" = 1: channel 3 counts pulses with Fmax = 2kHz
  • Set register "counter DI4: filter time" = 1: channel 4 counts pulses with Fmax = 2kHz

5.4 Analog Input

image-1591342412832.png

04 AI channels, no isolation (AI1 is a 4-20mA / 0-5 VDC / 0-10 VDC level sensor input)

LFC128-2-H10.png

Use DIP SW to configure Analog input: 0-10V, 0-20mA

 

sw.png

Value Type of AI
0

0-10 V

1

0-20 mA

Input type:

  • Measure voltage: 0-10V
  • Measure current: 0-20mA
  • The configuration for AI reads the same logical state as DI, but it is not isolated with a pulse range of 0-24V

Input impedance:

  • Measure voltage: 320 kΏ
  • Measure the current: 499 Ώ
5.4.1 Read the Analog value

Resolution 12 bits

Non-Linearity: 0.1%

Analog value in Modbus Memory Map: 0-3900

Analog value register in the Modbus Memory Map:

  • AI1 analog value: store the Analog value of channel 1
  • AI2 analog value: stores the Analog value of channel 2
  • AI3 analog value: store the Analog value of channel 3
  • AI4 analog value: store the Analog value of channel 4
5.4.2 AI configuration works as DI

No isolation

AI Configure AI to read the same logic state as DI with pulse amplitude from 0-24V

There are 2 counter threshold AIx: logic threshold 0 and counter AIx: threshold logic 1 in the modbus table: 0-4095

  • Analog Analog value of AI <counter AIx: threshold logic 0: is considered Logic 0 status of AI
  • Analog Analog value of AI> counter AIx: threshold logic 1: is considered to be Logic 1 state of AI
  • Counter AIx: threshold logic 0 = <Analog value of AI <= counter AIx: threshold logic 1: is considered to be the constant logic state

Logic Logical status value of AI in Modbus Memory Map table: 0-1

The register stores logical values ​​in Modbus Memory Map:

  • AI1___AI2: digital status: stores the logical state of channel 1 and channel 2.
      • H_byte: AI1
      • L_byte: AI2
  • AI3___AI4: digital status: stores the logical state of channel 1 and channel 2.
      • H_byte: AI3
      • L_byte: AI4
5.4.3 Pulse Counter AI max 10Hz

Counter value in Modbus Memory Map, when adding the number beyond the threshold, it will automatically return: 0 - 4294967295 (32bits)

The register that stores Counter value in the Modbus Memory Map cannot be erased:

  • Counter AI1: stores the logic state of channel 1
  • Counter AI2: save logic state of channel 2
  • Counter AI3: save logic state of channel 3
  • Counter AI4: save logic state of channel 4

The register that stores Counter value in the Modbus Memory Map cannot be erased:

  • None reset counter AI1: stores the logic state of channel 1
  • None reset counter AI2: stores the logic state of channel 2
  • None reset counter AI3: stores the logic state of channel 3
  • None reset counter AI4: save logic state of channel 4

5.5 Relay

image-1591341815045.png

04 channel Relay SPDT NO / NC

Contact rating: 2A / 24VDC, 0.5A / 220VAC

There are status LEDs:

  • Led on: Close Contact
  • Led off: Open Contact

Default Relay Register

Status of relays when resetting power supplies

3

Operate according to the Alarm configuration

Alarm Configuration:

  • HIHI : Relay 4 On
  • HI : Relay 3 On
  • LO : Relay 2 On
  • LOLO: Relay 1 On

5.6 Pulse Output

image-1591341459629.png

01 isolated open-collector channel

Opto-coupler: Source current Imax = 10mA, Vceo = 80V

Functions: On / Off, pulse generator, PWM

5.6.1 On/Off Function

Set the Open-collector register in the Modbus Memory Map table:

  • Set Open-collector register: 1 => Pulse Output ON
  • Set Open-collector register: 0 => Pulse Output OFF
5.6.2 Pulse generator

Pulse output transmits a maximum of 65535 pulses, with Fmax 2.5kHz

Configure the following registers in the Modbus Memory Map table:

  • Set register "open collector: pulse number": 0-65535 => Pulse Number = 65535: broadcast 65535 pulses
  • Set register "open collector: time cycle": (0-65535) x0.1ms => Time Cycle = 4: Fmax 2.5kHz
  • Set register "open collector: time on": (0-65535) x0.1ms => Time On: is the logic time 1 of the pulse
  • Set the register "open collector ctrl" = 3 => configure the Pulse Output to generate a pulse and start to pulse, generate a sufficient number of pulses in the "open collector: pulse number" register => stop pulse generator and register " open collector ctrl ”= 0
5.6.3 PWM

Max frequency 2.5kHz

Configure the following registers in the Modbus Memory Map table:

  • Set the register "open collector ctrl" = 2 => configure Pulse Output PWM function
  • Set register "open collector: time cycle": (0-65535) x0.1ms => Time Cycle = 4: Fmax 2.5kHz
  • Set register "open collector: time on": (0-65535) x0.1ms => Time On: is the logic time 1 of the pulse

6. Installation

6.1 Installation method

LFC128-2-H7.png

 Panel mount

6.2 Wiring with Level Sensor
LFC128-2-H10.png

7. Configuration

7.1 Home Screen

LFC128-2-H8.png

SCREEN: Switch to 2nd screen with more detailed information

ALARMS: Show Level Alert

HOME: Return to Home Screen

CONFIG. (Default Password: a): Go to Setting Screen

7.2 Setting screen (Default Password: a)

7.2.1 Screen 1

screen2.png

ADC: Raw signal value of channel AI1

Level (Unit): The level corresponds to the ADC signal after configuration

Decimal Places Level:Decimal number of digits after the dot of Level 0-3 (00000, 1111.1, 222.22, 33.333)

Unit level: level units, 0-3 (0: mm, 1: cm, 2: m, 3: inch)

In 1: Enter the ADC value after putting 4 mA / 0 VDC into AI1 for calibration at 0 level

Scale 1: The level value displayed corresponds to the value entered in In 1 (usually 0)

In 2: Enter the ADC value after putting 20 mA / 10 VDC into AI1 for calibration at Full level

Scale 2: The level value displayed corresponds to the value entered in In 2

Span Level: Maximum value of Level (Span Level ≥ Scale 2)

Decimal Places Volume: Decimal number of digits after the dot of Volume 0-3 (00000, 1111.1, 222.22, 33.333)

Unit Volume: units of volume 0-3 (0: lit, 1: cm, 2: m3, 3:%)

7.2.2 Screen 2

screen4.png

Level Hi Hi Set point (Unit): High High level of Alarm Level

Level Hi Hi Hys (Unit): High High level hysteresis of Alarm Level

Level Hi Set point (Unit): High level of Alarm Level

Level Hi Hys (Unit): High level hysteresis of Alarm Level

Level Lo Set point (Unit): Low level of Alarm Level

Level Lo Hys (Unit): Low level hysteresis of Alarm Level

Level Lo Lo Set point (Unit): Low Low level of Alarm Level

Level Lo Lo Hys (Unit): Low Low level hysteresis of Alarm Level

Alarm Mode: 0: Level, 1: Volume

Span Volume(Unit): Maximum value of the volume

7.2.3 Screen 3

screen3.png

Volume Hi Hi Set point (Unit): High High volume of Alarm Volume

Volume Hi Hi Hys (Unit): High High volume hysteresis of Alarm Volume

Volume Hi Set point (Unit): High volume of Alarm Volume

Volume Hi Hys (Unit): High volume hysteresis of Alarm Volume

Volume Lo Set point (Unit): Low volume of Alarm Volume

Volume Lo Hys (Unit): Low volume hysteresis of Alarm Volume

Volume Lo Lo Set point (Unit): Low Low volume of Alarm Volume

Volume Lo Lo Hys (Unit): Low Low volume hysteresis of Alarm Volume

Run Total: Run the total function. 0-1 (0: No 1: Yes)

7.2.4 Screen 4

screen5.png

Filling (Unit): Total function: total put into tank

Consumption (Unit): Total function: total consumption of the tank

Decimal Places Total: Decimal number of parameters Filling, Consumption, NRT Filling, NRT Consumption on display page (not the setting page)

Delta Total (Unit): Hysteresis level of the total function

Modbus Address: Modbus address of LFC128-2, 1-247

Modbus Baurate S1: 0-1 (0 : 9600 , 1 : 19200)

Modbus Parity S1: 0-2  (0: none, 1: odd, 2: even)

Modbus Baurate S2: 0-1 (0 : 9600 , 1 : 19200)

Modbus Parity S2: 0-2  (0: none, 1: odd, 2: even)

Num of Points: Number of points in the table to convert from level to volume, 1-166

7.2.5 Screen 5

screen6.png

Point 1 Level (Level Unit): Level at Point 1

Point 1 Volume (Volume Unit): The corresponding volume at Point 1

  •  
  •  
  •  

Point 166 Level (Level Unit): Fuel level at Point 166

Point 166 Volume (Volume Unit): The corresponding volume at Point 166

7.2.6 Screen 6

screen7.png

Password: Password to enter the Setting page, 8 ASCII characters

Tank Name: Tank name displayed on the main screen

8. Troubleshooting

No. Phenomena Reason Solutions
1 Modbus failed to communicate

Modbus LED Status:

  • LED is off: received no data
  • LED is blinking: the Modbus configuration is not the correct 
  • Check the connection
  • Check the Modbus configuration: Address, Baud Rate, Parity
2 Timeout Modbus Noise appears on the line Configure Baudrate 9600 and use a twisted pair cable with anti-jamming protection
3 Sensor Disconnected Sensor and LFC128 lost connection
  • Checking connection
  • Check sensor type (LFC128-2 only connects to 0-10VDC / 4-20mA analog sensor type)
  • Check the switch to see if it is turned on correctly
  • Check that the sensor connector is correct AI1
4 Linearization table error Error of conversion table from level to volume Check the configuration of the conversion table from level to volume