Gas Sensor with Modbus output MBRTU-G4-NH3
| SKU: MBRTU-G4-NH3 | Doc No: MBRTU-G4-NH3-DS-EN-10 |
IntroductionMBRTU-G4-NH3 is an electrochemical-type gas sensor with a high sensitivity to low concentrations of NH3 gas, high selectivity, and a stable baseline. It is powered by a wide range of power supplies 7..48VDC and gives output via RS485 ModbusRTU.
|
Typical ApplicationsAmbient Gas Monitoring in Facilities, Farm, Building, Factory, City...
|
![]() |
![]() |
Specification
| SENSOR SPECIFICATION | |
| Sensor type | Daviteq Seri-4 electrochemical gas sensor |
| Nominal range | 0-100 ppm |
| Maximum overload | 200 ppm |
| Resolution | 0.1 ppm |
| T90 response time | < 35 s |
|
Typical Baseline Range (pure air, 20°C) |
-3.0 ppm .. + 3.0 ppm |
| Repeatability | < 3% of reading |
| Linearity | 5% of full scale |
| Temperature compensation | Yes |
| Relative humidity range |
15 % to 90 % RH non-condensing |
| Temperature range |
-10 °C to 50 °C |
| Pressure range |
Atmospheric ± 10% |
| Humidity effect (Abrupt changes in rel. humidity causes a short-term transient signal) |
< 4 ppm |
|
Expected Operation Life |
2 years in the air |
|
Expected Long-Term Output Drift in air |
< 5 % of reading loss per 6 months |
| Filter & Protector | Nylon filter |
| Sensor housing / Rating | Plastic / IP67 |
| OTHER SPECIFICATION | |
| Communication Port | RS485, ModbusRTU protocol, max 19200 baud |
| Power supply | 9..36VDC, avg. < 200mA |
| Connector | M12-male 4-pin Code A |
| Working temperature | 0 .. 50 oC |
| Working humidity | 15 .. 90% RH |
| Housing | Thermal Plastic |
| Housing Rating | IP67 |
| Dimension | H150xD30 |
| Net weight | <200 grams |
CROSS SENSITIVITY DATA
The table below does not claim to be complete. Interfering gases should not be used for calibration.
|
Interfering Gas |
Concentration (ppm) | Reading (ppm) |
| Cl2 | 20 | -55 |
| CO | 300 | 0 |
| CO2 | 20000 | 0 |
| H2 | 200 | 0 |
| H2S | 20 | 7 |
| NO | 20 | -1 |
| NO2 | 20 | -20 |
| SiH4 | 10 | 0 |
| SO2 | 20 | -7 |
ORDERING CODE
| Item code | Descriptions |
|
MBRTU-G4-NH3-100-01 |
MODBUSRTU OUTPUT AMMONIA GAS NH3, 0-100PPM, RS485/MODBUSRTU, 7..48VDC SUPPLY, M12-M CONNECTOR |
|
MBRTU-G4-H2S-50-01 |
MODBUSRTU OUTPUT H2S GAS, 0-50PPM, RS485/MODBUSRTU, 7..48VDC SUPPLY, M12-M CONNECTOR |
|
Please select below M12 cable with different lengths |
|
|
2M-FM12CAB4X0.25 |
M12 4PIN FEMALE ASSEMBLY CONNECTOR WITH SOLDERING TERMINALS AND CODING A AND CONTROL CABLE CU/PVC/OS/PVC 4X0.25MM2, L=2M, ROHS, SHIELD 80% |
|
5M-FM12CAB4X0.25 |
M12 4PIN FEMALE ASSEMBLY CONNECTOR WITH SOLDERING TERMINALS AND CODING A AND CONTROL CABLE CU/PVC/OS/PVC 4X0.25MM2, L=5M, ROHS, SHIELD 80% |
|
10M-FM12CAB4X0.25 |
M12 4PIN FEMALE ASSEMBLY CONNECTOR WITH SOLDERING TERMINALS AND CODING A AND CONTROL CABLE CU/PVC/OS/PVC 4X0.25MM2, L=10M, ROHS, SHIELD 80% |
Link for full datasheet: