Process Optical Dissolved Oxygen Sensor with Modbus output MBRTU-PODO Version 2

SKU: MBRTU-PODO Doc No: MBRTU-PODO-DS-EN-20

Introduction

MBRTU-PODO is Process Optical Dissolved Oxygen Electrode with optic technology is based on the proven method whereas oxygen concentration is determined by the luminescent quenching of a dye embedded on the sensor surface. Unlike polarographic or galvanic sensors, this optical sensor does not require filling solutions nor a “warm-up” time. The electrode comes with 1/2” NPT threads, a durable stainless steel body and is submersible. Output is Modbus RTU for easily integrating with any PLC, controller, SCADA, BMS or IoT gateway.

 

  • Affordable, complete electrode system

  • Fully documented RS485 output for existing PLC/controllers/monitors

  • No electrolyte solution to replenish

    Replaceable sensor cap with >2 year life expectancy

  • No calibration or replacement sensor cap for at least 1 year in most applications

  • Saltwater compensation

  • On-probe pressure sensor for compensation

  • Sample flow not necessary for measurement accuracy

  • Standard ModbusRTU output;

Typical Applications

MBRTU-PODO is used in monitoring of Dissolved oxygen in:

 

Waste water;

Aquaculture;

...

PODO-V2-1.jpg PODO-V2-2.jpg
with Protective cover

PODO-V2-3.jpg

Sensor cap

PODO-V2-4.jpg

with 4-20mA converter

 
Specification
ODO SENSOR SPECIFICATION
Sensing Technology Optical sensor
Measuring range 0 - 20 ppm or 0-200% Saturation
Resolution 0.01 ppm, 0.1 oC
Accuracy +/- 0.3% FS, +/- 0.3 oC
Response Time T90 < 50s
Sensor cap life > 1 year under normal condition
Working temperature 0 .. 50 oC
Process connection 1/2" NPT
Wetted parts 316SS
Sensor Cable 10m standard
Rating IP68
Sensor Dimension D30 x 120 (mm)
Sensor net weight < 350 grams
Output RS485, ModbusRTU protocol, 9600, 8, 1, None
Power supply 12..24VDC, avg. < 50mA
OPTIONAL CONVERTER TO 4-20mA
Size 83*58*33.5mm
Output 4-20mA
Supply 12-24VDC, < 20mA
Ordering Code
Item code Descriptions

MBRTU-PODO-03

PROCESS OPTICAL DISSOLVED OXYGEN SENSOR IP68, 1/2" NPT SUBMERSIBLE, MODBUSRTU RS485 OUTPUT, 12-24VDC, 10M CABLE

Accessories

RS485-FM12-USB-1

RS485 FEMALE M12 4-PIN, CODING A TO USB CABLE WITH POWER ADAPTER 12VDC/2.0A FOR CONFIGURATION

* Configuration cable for pH sensor, Windows' software is free. Contact our sales for more information.


logo-01.png

Daviteq Technologies Inc

 

IconWebsite.png  www.daviteq.com   |   IconEmail.png  info@daviteq.com