DAVITEQ CHLORINE Cl2 GAS SENSOR, 20 PPM, SERI-4

SENSOR SPECIFICATION
MEASURING SPECIFICATION  
Sensor type Daviteq Seri-4 electrochemical gas sensor
Nominal range 0-20 ppm
Maximum overload 200 ppm
Resolution 0.01 ppm
T80 response time < 60 s

Typical Baseline Range (pure air, 20°C)

-0.1 ppm .. +0.2 ppm
Repeatability < 2% of reading or 0.05ppm whichever greater
Accuracy +/- 5% of reading
Zero stability 0 .. 0.05 ppm in pure Air, 20oC
Temperature compensation Yes
WORKING CONDITIONS  
Relative humidity range

15 % to 90 % RH non-condensing

Temperature range

-40 °C to 50 °C 

Pressure range

Atmospheric ± 10% 

Humidity effect

None

SENSOR LIFETIME  

Expected Operation Life

2 years in the air 

Expected Long-Term Output Drift in air

< 2 % of reading loss per month
CROSS SENSITIVITY DATA

The table below does not claim to be complete. Interfering gases should not be used for calibration.

Interfering Gas  Concentration (ppm) Reading (ppm)
Br2 10 2.5
C2H4 100 0
CH2O 7 0
ClO2 3 ~3
CO 300 0
Ethanol (C2H5OH) 60 0
F2 8 ~8
H2 100 0
H2S 20 < -20
HCl 20 0
NH3 80 0
NO 50 0
NO2 20 ~20
O3 1 ~1
SO2 5 0