Manual for Sigfox-Ready Air/Gas Flow Sensor - WSSFC-M12F-AFD | FW1
THIS IS OBSOLETE MANUAL
Please access https://www.iot.daviteq.com/wireless-sensors for updated manual
Thank you very much for choosing Daviteq Wireless Sensors. We are the leading wireless sensor manufacturer in the World. We have a wide range of wireless sensors which support different connectivity like LoRaWAN, Sigfox, Sub-GHz, NB-IoT...Please find out more information at this link.
This manual is applied to the following products
Item code | HW Version | Firmware Version | Remarks |
WSSFC-M12F-AFD | 1 |
Product Features
Connectivity Type | Sigfox |
Product Type | 2 parts |
Mounting Type | Direct process mounting for the whole set |
Powered by | 2 x AA batteries 1.5V |
Information Changes in this version v.s previous version
Item | Changes | Changed by | Changed Date | Approved by | Approved Date |
1 | Initial version | D.Q.Tuan | 26-08-2022 | N.V.Loc | 05-09-2022 |
To use this product, please refer step by step to the below instructions.
1. Quick Guide
Reading time: 10 minutes
Finish this part so you can understand and put the sensor in operation with the default configuration from the factory.
1.1 What is the Sigfox-Ready AFD Air/Gas Flow Sensor and its principle of operation?
WSSFC-M12F-AFD is a Sigfox-Ready node to work with an AFD probe for measuring the Air/Gas Flow in a pipe or duct.
It is battery-operated and able to connect to any Sigfox network in the World. It supports all frequency zones such as RC1, RC2, RC3c, RC4, RC5, RC6, and RC7.
For the principle operation of the AFD probe, please refer to this link.
1.1.1 What are the typical applications of this sensor?
Please refer to this link for typical applications.
1.1.2 When does the device send uplink messages?
The device will send uplink messages in the following cases:
- Case 1: After power-up in the 60s, the device will send the first message called START_UP. The payload will tell the user the HW version, FW version, and current configuration of the device;
- Case 2: Then, in every interval time (pre-configured), for example, 10 minutes, it will send the message called CYCLIC_DATA. The payload will tell the user the following data like measured value (AC current value), battery level, alarm status...
To change the cycle of data sending, you can change the value of the parameter: CYCLIC_DATA_PERIOD (default is 600 seconds).
- Case 3: If the Alarm function was enabled (in the configuration of the sensor), if the measured value passed the threshold, it will send the uplink message immediately. This message is called ALARM. The payload also tells the user the data like measured value (AC current value), battery level, alarm status...
The alarm thresholds can be changed via downlink or offline tools.
- Case 4: The HEART_BEAT uplink message will be sent once a day (the default setting can be changed in configuration) to allow the Sigfox back-end system can send the downlink message for changing the configuration of the sensor. Please refer to the downlink section for more details. The uplink payload will tell the user the HW version, FW version, and current configuration of the device;
- Case 5: During commissioning, testing, or calibration sensor, the user can force the device to send the uplink message to get the data immediately. This message is called FORCE_DATA. The payload will provide data like raw measured value, scaled measured value, battery level, alarm status... It can be forced by applying the magnet key on the reed switch in 1s;
- Case 6: If users want to change the configuration immediately, they don't need to wait up to 1 day for the HEART_BEAT message, instead they can force the device to send a special uplink message so that the device can get the new downlink message. This uplink message is named PARAMETERS_UPDATE. It can be forced by applying the magnet key in more than 5s.
1.1.3 The important configuration parameters
The sensor was pre-configured at the factory with default values for configuration parameters that meet most use cases. However, depending on the specific use case, the customer can adjust those parameters. Please refer to section 3.2 for more details.
1.1.4 What kind of battery is used for this sensor?
The sensor is powered by 2 x AA 1.5V batteries for many years of operation. We do recommend using Energizer L91 battery which is very popular and high performance. This battery has a capacity of up to 3500mAh with a working temperature range from -40 to +60 oC. The instruction for installing the batteries is in this link.
Figure 1. Battery Energizer L91
For Battery life estimation, please refer to this link.
1.2 What's in the package?
The package includes:
01 x Main device
01 x Magnet key
01 x Wall mounting bracket and screws
01 x AFD flow sensor probe (order separately with item code AFD-....)
Figure 2. Product package of WSSFC-M12F-AFD
Figure 3. Product package of AFD-....
1.3 Quick Test
With the default configuration, the device can be connected quickly to the Sigfox Network by the following steps.
Step 1: Prepare the values of communication settings:
Device ID |
Get Devive ID on the device nameplate |
Device PAC |
Get Devive PAC on the device nameplate |
Note: All Sigfox sensors are pre-configured with the correct RC before delivery. The settings of Device ID, Device PAC, and RC could also be read from the device memory map. Please reference section 3.2 Sensor configuration for details.
Step 2: Add the device to Sigfox Backend
Please refer to this link for details
Step 3: Install the batteries to the device
Please refer to this link for instructions on battery installation.
After installing the battery in 60 seconds, the first data packet will be sent to the Sigfox network. After receiving the first data packet, the time of another packet depends on the value of the parameter: CYCLIC_DATA_PERIOD. Additionally, you can use a Magnet Key to force the device to send data instantly.
Step 4: Decode the payload of receiving package
Please refer to section 1.4 Uplink Payload and Data Decoding for details of decoding the receiving packet to get the measured values.
1.4 Uplink Payload and Data Decoding
For the Uplink Payload structure, please refer to this link.
Note: Please select the right Payload document to suit the FW version of the sensor
1.5 Sensor Installation
DIMENSIONS OF PRODUCT
Figure 4. Dimensions of WSSFC-M12F-AFD
Figure 5. Dimensions of AFD-0200
1.5.1 Installation
The Sigfox-Ready AFD Air/Gas flow sensor combines a wireless transmitter WSSFC-M12F-AFD and an AFD Air/Gas Flow Sensor. Therefore, the installation will be divided into 02 parts:
+ Installation for AFD Air/Gas Flow Sensor: these steps are to make sure the device to measure correctly. Please follow this link.
+ Installation for the wireless transmitter: these steps ensure the device sends data successfully. Please see below the steps
-
- Insert the batteries into the wireless transmitter and check the system to see whether the wireless transmitter already sent the first message to the system. Please follow this link to learn how to install the batteries.
ATTENTION:
REVERSED POLARITY OF BATTERIES IN 10 SECONDS CAN DAMAGE THE SENSOR CIRCUIT!!!
- Insert the batteries into the wireless transmitter and check the system to see whether the wireless transmitter already sent the first message to the system. Please follow this link to learn how to install the batteries.
-
- Attach the wireless transmitter to the AFD probe as below figures.
Figure 6. Complete set of WSSFC-M12F-AFD and AFD-0200
1.5.2 Device calibration & configuration
Please refer to this link.
2. Maintenance
2.1 Troubleshooting
- Problems with Sigfox communication like not receiving the packets...please refer to this link to troubleshoot the device.
- Problems with the sensor functions like not measuring or inaccurate measuring....please refer to this link to troubleshoot the sensor part.
2.2 Device maintenance
2.2.1 Maintenance for Wireless transmitter WSSFC-M12F-AFD
Maintenance works | Yes/No |
Descriptions |
Consumable parts replacement | Yes |
The battery is the only part need to check the lifetime to replace. Check the battery status on the back-end system. |
Cleaning device | No |
|
Re-calibration / Re-validation | No | No calibration is required for the wireless transmitter. |
2.2.2 Maintenance for AFD flow probe
Please refer to this link.
3. Advanced Guide
3.1 Operating principle of the Sigfox-Ready AFD Air/Gas Flow Sensor
3.1.1 Operating principle of the complete device
The Daviteq Sigfox-Ready AFD Air/Gas Flow sensor comprises 02 parts connected together as shown below picture.
- The Daviteq Sigfox-Ready wireless transmitter WSSFC-M12F-AFD
- The Daviteq AFD Air/Gas Flow Sensor AFD-...
Figure 7. Complete set of WSSFC-M12F-AFD and AFD-0200
The AFD Air/Gas Flow Sensor measures pressure and temperature... in the duct or pipe.
The Sigfox-Ready wireless transmitter is to read the parameters of the probe like differential pressure, temperature, and error code... and performs the scaling and calculation to deliver the fluid velocity in the duct or pipe.
3.1.2 Operating principle of AFD Air/Gas Flow Sensor
To understand how the AFD Air/Gas Flow Sensor works, please refer to this link for a complete understanding of this measuring technique.
3.1.3 Some important configuration parameters
Below are some important configuration parameters which affect the operation of the device like battery life, measurement accuracy, and alert threshold.
For Battery life estimation, please refer to this link.
- measure_period | Default = 600s
This is the time period for the wireless transmitter to wake up and take the measurement from the transducer. The default value is 600s. Users can reduce this value, but smaller value, shorter battery life! - cyclic_data_period | Default = 1800s
Interval time to send an uplink message regardless of any conditions - sensor_boot_time | Default = 200mS
This value will affect the measurement accuracy. DO NOT change this value!
- density_of_fluid | Default = 1.225 (Air)
This value will affect the measurement accuracy.
Those configuration parameters can be changed by downlink or offline tools. For more other configuration parameters, please refer to the next section.
3.2 Sensor Configuration
3.2.1 How to configure the Sigfox-Ready AFD Air/Gas Flow Sensor?
Sensor configuration can be configured in 02 methods:
- Method 1: Configuring via Downlink message. Please find the instructions in this link, but please take note of the FW version of the Document.
- Method 2: Configuring via offline cable.
Note: THE SENSOR IS ONLY ACTIVE FOR OFFLINE CONFIGURATION IN THE FIRST 60 SINCE POWER UP BY BATTERY OR PLUGGING THE CONFIGURATION CABLE.
3.2.2 What parameters of the device are configured?
- Some parameters are read-only, and some are read and writeable.
- To read the parameters, use the off-line cable as above instruction.
- Via uplink message, users can read only one parameter, which is the CURRENT_CONFIGURATION.
Below tables are the lists of the parameters of the device.
Read-only Parameter Table
Modbus Register (Decimal) |
Modbus Register (Hex) |
Function Code (Read) |
No. of Registers |
Description |
Range |
Format |
Property |
Comment |
2 |
2 |
3 |
4 |
FW_VERSION |
|
string |
Read |
|
6 |
6 |
3 |
2 |
HW_VERSION |
|
string |
Read |
|
8 |
8 |
3 |
2 |
DEVICE_ID |
|
hex |
Read |
Product ID |
10 |
A |
3 |
4 |
DEVICE_PAC |
|
hex |
Read |
Product PAC |
14 |
E |
3 |
1 |
SENSOR_TYPE |
1-255 |
uint16 |
Read |
Sensor or Input Type |
Read/Write Parameter Table
Modbus Register (Decimal) |
Modbus Register (Hex) |
Function Code (Read) |
Function Code (Write) |
No. of Registers |
Description |
Range |
Default |
Format |
Property |
Comment |
270 |
10E |
3 |
16 |
4 |
CURRENT_CONFIGURATION |
|
|
hex |
Read/Write |
Check the Payload Document section: 5.Payload for downlink message for more information |
274 |
112 |
3 |
16 |
1 |
SERVER_CONFIG |
|
0 |
uint16 |
Read/Write |
0: Send to Sigfox Network 1: Send to Dongle |
276 |
114 |
3 |
16 |
1 |
RADIO_CONFIG |
1-4 |
4 |
uint16 |
Read/Write |
RC zones selection 1, 2 , 3, 4 is RC1, RC2, RC3s, RC4 |
277 |
115 |
3 |
16 |
1 |
TX_POWER |
|
20 |
int16 |
Read/Write |
RF Tx power |
278 |
116 |
3 |
16 |
2 |
CONSTANT_A |
|
1 |
float |
Read/Write |
Constant a for scaling measured value |
280 |
118 |
3 |
16 |
2 |
CONSTANT_B |
|
0 |
float |
Read/Write |
Constant b for scaling measured value |
282 |
11A |
3 |
16 |
2 |
HIGH_CUT |
|
1E+09 |
float |
Read/Write |
High cut value for the calculated value |
284 |
11C |
3 |
16 |
2 |
LOW_CUT |
|
0 |
float |
Read/Write |
Low cut value for the calculated value |
286 |
11E |
3 |
16 |
2 |
SENSOR_BOOT_TIME |
|
200 |
uint32 |
Read/Write |
Boot time of sensor/input, in ms |
307 |
133 |
3 |
16 |
1 |
TEMPERATURE_OFFSET_X10 |
|
0 |
int16 |
Read/Write |
Offset adjustment for measured temperature value |
308 |
134 |
3 |
16 |
2 |
DENSITY_OF_FLUID |
|
1.225 |
float |
Read/Write |
Fluid Density, default is Air |
3.3 Calibration for Sigfox-Ready AFD Air/Gas Flow Sensor
Please refer to this link.
4. Product specification
Please refer to the detailed specifications in this link.
5. Warranty and Support
For warranty terms and support procedures, please refer to this link.
6. References
Use-cases:
Case studies:
White-papers:
END.