Sample HTML table for troubleshooting

No. Phenomena Reason Solution
    1 Node does not send RF to the base station periodically and LED does not blink There is no power supply or battery is flat Measure the voltage of the battery OR  check the installation of the battery OR check the power supply if applicable
The configuration sending cycle is incorrect or is accidentally changed Check the sending cycle configuration by offline tool
Hardware node is defective Check with offline tool and/or check visually any burnt mark, disconnection, heat on the hardware. Contact manufacturer for repair or replacement if needed
The node is accidentally in black-list of Sigfox operator Check with the Sigfox operator
The Sigfox base stations at the node location are out of operation Check the operation of another node at the same location or check with Sigfox operator about status of the Sigfox base station
New objects are added between the sensor and Sigfox base station Check and remove the obstruction objects at site
    2 Node does not send RF to the base station according to the alarm, LED does not blink The alarm threshold values are incorrect and/or alarm function is disabled Check alarm threshold values and alarm enable on start up message or heartbeat message or parameter update message or on node memory map with offline tool
The number of real alarms during 24-hour are greater than daily alarm limit Check the configuration for the maximum number of alarms per day on node memory map
    3 Node does not send RF to the base station when activated by the magnetic switch, LED does not blink The magnetic switch has malfunctioned Read the status of the magnetic switch via Modbus (when powering or attaching the battery) to see if the magnetic switch is working OR check the magnetic switch visually
Magnet key is not in right touching-position on node housing Put the correct position for the magnet key on the node housing
    4 Node has blinked LED when sending RF but the base station cannot receive the data The number of sending message during 24-hour are greater than the limit RF packages of uplink per day (max 140 packages/day) Check on the base station whether the event message exceeds the number of RF packets
    5 Node has sent RF but the LED does not blink The LED is malfunctioned Contact manufacturer for repair or replacement
    6 The node does not send RF and the RF module is too hot Battery is inserted in the wrong direction Check battery polarity
Working environment of the node is too hot Improve ventilation to lower environment temperature
Hardware node is defective Contact manufacturer for repair or replacement
    7 RSSI is weak and often loses data Distance between Node and Base station is too far Check the location of the Sigfox node and relocate it if applicable
There are many obstructions between the node and Sigfox base station Check and remove the obstruction objects at site or re-locate the position of the node if applicable
New objects are added between the sensor and Sigfox base station Check and remove the obstruction objects at site
There is a problem of Sigfox antenna connection Check the antenna connector on the printed circuit board
    8 The measurement values from the sensor do not change and keep constant values for a long time Sensor got failure Check the sensor visually or/and with offline tool. Contact manufacturer for repair or replacement if needed
Sensor cable is broken Check sensor cable. Contact manufacturer for repair of replacement if the cable is broken
The sensor connector is not connected firmly Check sensor connector and contact manufacture for repair of replacement if the connector is broken
Some sensor measurement settings such as CONSTANT_A, CONSTANT_B, LOW_CUT, HIGH_CUT are misconfigured Check and correct right sensor measurement configurations