Sample HTML table for troubleshooting
No. | Phenomena | Reason | Solution |
---|---|---|---|
1 | Node does not send RF to the base station periodically and LED does not blink | There is no power supply or battery is flat | Measure the voltage of the battery OR check the installation of the battery OR check the power supply if applicable |
The configuration sending cycle is incorrect or is accidentally changed | Check the sending cycle configuration by offline tool | ||
Hardware node is defective | Check with offline tool and/or check visually any burnt mark, disconnection, heat on the hardware. Contact manufacturer for repair or replacement if needed | ||
The node is accidentally in black-list of Sigfox operator | Check with the Sigfox operator | ||
The Sigfox base stations at the node location are out of operation | Check the operation of another node at the same location or check with Sigfox operator about status of the Sigfox base station | ||
New objects are added between the sensor and Sigfox base station | Check and remove the obstruction objects at site | ||
2 | Node does not send RF to the base station according to the alarm, LED does not blink | The alarm threshold values are incorrect and/or alarm function is disabled | Check alarm threshold values and alarm enable on start up message or heartbeat message or parameter update message or on node memory map with offline tool |
The number of real alarms during 24-hour are greater than daily alarm limit | Check the configuration for the maximum number of alarms per day on node memory map | ||
3 | Node does not send RF to the base station when activated by the magnetic switch, LED does not blink | The magnetic switch has malfunctioned | Read the status of the magnetic switch via Modbus (when powering or attaching the battery) to see if the magnetic switch is working OR check the magnetic switch visually |
Magnet key is not in right touching-position on node housing | Put the correct position for the magnet key on the node housing | ||
4 | Node has blinked LED when sending RF but the base station cannot receive the data | The number of sending message during 24-hour are greater than the limit RF packages of uplink per day (max 140 packages/day) | Check on the base station whether the event message exceeds the number of RF packets |
5 | Node has sent RF but the LED does not blink | The LED is malfunctioned | Contact manufacturer for repair or replacement |
6 | The node does not send RF and the RF module is too hot | Battery is inserted in the wrong direction | Check battery polarity |
Working environment of the node is too hot | Improve ventilation to lower environment temperature | ||
Hardware node is defective | Contact manufacturer for repair or replacement | ||
7 | RSSI is weak and often loses data | Distance between Node and Base station is too far | Check the location of the Sigfox node and relocate it if applicable |
There are many obstructions between the node and Sigfox base station | Check and remove the obstruction objects at site or re-locate the position of the node if applicable | ||
New objects are added between the sensor and Sigfox base station | Check and remove the obstruction objects at site | ||
There is a problem of Sigfox antenna connection | Check the antenna connector on the printed circuit board | ||
8 | The measurement values from the sensor do not change and keep constant values for a long time | Sensor got failure | Check the sensor visually or/and with offline tool. Contact manufacturer for repair or replacement if needed |
Sensor cable is broken | Check sensor cable. Contact manufacturer for repair of replacement if the cable is broken | ||
The sensor connector is not connected firmly | Check sensor connector and contact manufacture for repair of replacement if the connector is broken | ||
Some sensor measurement settings such as CONSTANT_A, CONSTANT_B, LOW_CUT, HIGH_CUT are misconfigured | Check and correct right sensor measurement configurations |