New Page
Action | Settings | Start Address (Decimal) | Start Address (Hex) | Number of Registers | Data type | How to change offline with configuration cable | How to change online with downlink |
Change LoRaWAN App EUI | lora appEUI | 270 | 10E | 4 | hex | Write new value (16 hexadecimal value) to "lora appEUI" setting with function of 16 | Unavailable |
Change LoRaWAN App Key | lora appKey | 274 | 112 | 8 | hex | Write new value (32 hexadecimal value) to "lora appKey" setting with function of 16 | Unavailable |
Change LoRaWAN region | region | 317 | 13D | 1 | uint16 | Write new value to "region" setting with function of 16. The value list for corresponding region as below 1: AS923-1, 2: KR920, 3: AU915, 4: US915, 5: EU868, 6: IN865, 7: RU864, 8: AS923-2, 9: AS923-3, 10: AS923-1 Japan |
Unavailable |
Change Spread Factor (SF) or data rate | data rate | 318 | 13E | 1 | uint16 | Write new value to "data rate" setting with function of 16. Written value versus SF/data rate based on LoRaWAN region as below: * FOR US915: 0 = 980 bps = SF10, 1 = 1760 bps = SF9, 2 = 3125 bps = SF8, 3 = 5470 bps = SF7 * FOR AS923, AU915: 2 = 980 bps = SF10, 3 = 1760 bps = SF9, 4 = 3125 bps = SF8, 5 = 5470 bps = SF7 * FOR Other Region: 0 = 250 bps = SF12, 1 = 440 bps = SF11, 2 = 980 bps = SF10, 3 = 1760 bps = SF9, 4 = 3125 bps = SF8, 5 = 5470 bps = SF7 |
Send downlink with below new hexadecimal value using port 1 (default port): 3E02000100000005 to write 1 3E02000200000005 to write 2 3E02000300000005 to write 3 3E02000400000005 to write 4 3E02000500000005 to write 5 Written value versus SF/data rate based on LoRaWAN region as below: * FOR US915: 0 = 980 bps = SF10, 1 = 1760 bps = SF9, 2 = 3125 bps = SF8, 3 = 5470 bps = SF7 * FOR AS923, AU915: 2 = 980 bps = SF10, 3 = 1760 bps = SF9, 4 = 3125 bps = SF8, 5 = 5470 bps = SF7 * FOR Other Region: 0 = 250 bps = SF12, 1 = 440 bps = SF11, 2 = 980 bps = SF10, 3 = 1760 bps = SF9, 4 = 3125 bps = SF8, 5 = 5470 bps = SF7 |
Turn ON Adaptive Data Rate (ADR) | frequency channels for EU868 IN865 RU864 KR920 AS923 AU915 US915 AND adaptive data rate |
321 & 320 | 141 & 140 | 1 & 1 | uint16 & uint16 | Write value of 0 to "frequency channels for EU868 IN865 RU864 KR920 AS923 AU915 US915" setting with function of 16 AND then Write value of 1 to "adaptive data rate" setting with function of 16 |
Send first downlink with hexadecimal value of 4102000000000005 to device then send second downlink with the value of 4002000100000005 using port 1 (default port) |